1st Blower Door Test

The Initial Blower Door Test

Airtightness is of a building is related the the overall comfort of a building. The tighter the house, the less drafty it is and the more comfortable it is. In this Blower Door test we will be verifying the tightness of the primary air barrier, and sealing any holes we may have. It is much easier to seal them now, than after the insulation is in and the drywall is up.

The blower door is a diagnostic tool used to measure how tight (or leaky) a structure is. You should see a blower door done when you have an energy audit done on your home or if you own a Certified Energy Star, LEED or NAHB Green Homes you have had this test performed on your house (probably before you moved in). 

A few acronyms before I move on:
ACH50 - Air Changes Per Hour at 50 Pascals - With a blower door running at 50 Pascals (forcing a 20-25 mph wind on all 6 sides of the house at once). The number time time you will entirely replace the air inside the house in 1 hour
CFM50 - Cubic Feet Per minute at 50 Pascals - With a blower door running at 50 Pascals (forcing a 20-25 mph wind on all 6 sides of the house at once). The number of cubic feet of air moving though the blower door fan (and thus the amount of air being drawn into the house) in 1 minute

There are limits to each of the above programs
 - NYS Building Code is 7 ACH50 - or - Visual Inspection (99% of homes is a visual inspection)
 - LEED and NAHB Green are on a sliding scale (the tighter you are, the more points you get - and you may not need any of those points to achieve the certification) - so just because you have a Green Home, or a LEED home does not make it a Tight Home
 - EPA's Energy Star (in our area of the country) is 4 ACH50

However none of the is even close to the Passive House Standard. 

To meet Passive House Standards the house has to be 0.6 ACH50 or lower.

The blower door test will give you a CFM50 (cubic feet per minute at 50 Pascal's pressure difference between the inside and outside). Then the volume of air in the house must be calculated.

Calculating the Volume:
RESNET, BPI and ASTM standards calculates the Volume fairly similarly:
Measure the house from the outside, Measure the height from the basement slab to the upper ceiling and boom you have your volume. Pretty Easy, pretty straight forward

Passive House does things a little different. The measurements are all taken from the inside (since walls are so thick) and excludes the area's for interior walls. 

How much of an impact does this have on our house??
RESNET, BPI and ASTM standards has a volume of:                                      38,698 CUFT. 
Passive House Standard has a volume of:                                                         27,299 CUFT.

That is almost a 30% difference! 

This impacts the calculation quite a bit since:

So the Passive House Standard is even tighter than you'd expect!

OK - So enough "Technical Information" Lets see house we did!

Test Results:
We need to be under 273 CFM50 at the end of the build, our Goal for this test is 150 CFM50.

Here is our prep:
We sealed off the:
Front Door

Large Basement Window

Plumbing Penetrations

Small Basement Window

We chose to run the test out of the small basement window using the "Minneapolis Duct Blaster"
 

Here is our test result for today:

83 CFM50
0.129 ACH50 - per RESNET Standards
 0.182 ACH50 - per Passive House Standards

We determined the test to be a HUGE Success. We also did a little bit of air sealing and brought the test down to 73 CFM50

With the initial Blower Door test complete we can now continue installing all of the windows - my next post will discuss the installation procedure

Comments

Popular posts from this blog

Window Installation

With all of the engineering and design that goes into a house like this, why would window installation be any different? EVERYTHING in a passive house is modeled, examined, and optimized thermodynamically. For now we will be talking about the thermodynamic analysis of the Passive House Windows and how this translates to the positioning of the windows within the wall system. A typical new construction window comes with a nailing flange that is part of the frame of the window. This requires the window to be nailed directly to the wall, resulting in the window being flush with the outer edge of the exterior wall. Passive House windows don't come with the nailing flange, this allows flexibility in location of installation within the wall system. The fact is, in a thick wall (12 inches or more, further details on wall thickness will be addressed in a later post) you typically don't want to install the window on the outside of your wall. You want to install the window in the middle o...

Wall Assembly 1

Double Wall Construction Maybe I am biased to double wall construction because the company I work for Airtight Services  is a cellulose insulation company; but it is still probably the most cost effective way to achieve the R-values necessary for Passive House. Based on our energy model we needed to achieve about an R-54 wall. There were a couple options: 2x6 wall with 6" of polyisocyanurate rigid foam to the outside There are some more difficult window installation details when your window is cantilevered over nothing but foam. Some long screws are need to attached a furring strip over the rigid foam (9" long) and those can add considerable cost to the project - upwards of $0.75 each The labels on rigid foam insulation scared me a little bit too -  15 YEAR LIMITED THERMAL WARRANTY Polyisocyanurate has the WORST embodied energy of the good types of insulation meaning it takes the most amount of energy to make relative to how much it will save This graph was posted on Green Bu...