Blower Door 2

2nd Blower Door Test:

Thanks to all for the great turn out for the open dining room! We estimate there was about 150 people who came to check out the progress. No doubt this was a motivator for us to keep up the work and keep the blog up to date! Thank you!

After everyone left on Saturday we sealed off the open plumbing drains and the attic access hole and performed another blower door test. 

Our 1st Test Results:

  • Only the 3 1st floor southern windows were installed
  • There were zero penetrations in the zip system
  • The house volume was calculated to be:
    • RESNET, BPI and ASTM standards                                     38,698 CUFT
    • Passive House Standard                                                        27,299 CUFT
  • The Blower Door number was:
    • 83 CFM50 (we did get it down to 73 CFM50
  • The Air Changes per hour came out to:
    • 0.11 ACH50 - RESNET, BPI and ASTM standards
    • 0.16 ACH50 - Passive House Standard
Our 2nd Test Results:
  • 2 Exterior Hose Bibs have been installed
  • Multiple Electrical penetrations have been installed (including the services line)
  • All 1st and 2nd floor windows and doors are installed (except front door)
  • The outer wall assembly has been insulated with dense packed cellulose 
  • Our rain screen has been installed and taped
  • The volumes remain the same:
    • RESNET, BPI and ASTM standards                                     38,698 CUFT
    • Passive House Standard                                                        27,299 CUFT






We are still at essentially the SAME blower door number!! 
  • The Air Changes per hour came out to:
    • 0.11 ACH50 - RESNET, BPI and ASTM standards
    • 0.16 ACH50 - Passive House Standard

To put this in perspective - we have an "equivalent leakage area" of 4 square inches

We will be working this week to get the remaining above grade walls insulated with damp spray cellulose as well as the sound deadening walls. I will be posting some more on this process soon!

Comments

Popular posts from this blog

Window Installation

With all of the engineering and design that goes into a house like this, why would window installation be any different? EVERYTHING in a passive house is modeled, examined, and optimized thermodynamically. For now we will be talking about the thermodynamic analysis of the Passive House Windows and how this translates to the positioning of the windows within the wall system. A typical new construction window comes with a nailing flange that is part of the frame of the window. This requires the window to be nailed directly to the wall, resulting in the window being flush with the outer edge of the exterior wall. Passive House windows don't come with the nailing flange, this allows flexibility in location of installation within the wall system. The fact is, in a thick wall (12 inches or more, further details on wall thickness will be addressed in a later post) you typically don't want to install the window on the outside of your wall. You want to install the window in the middle o...

Wall Assembly 1

Double Wall Construction Maybe I am biased to double wall construction because the company I work for Airtight Services  is a cellulose insulation company; but it is still probably the most cost effective way to achieve the R-values necessary for Passive House. Based on our energy model we needed to achieve about an R-54 wall. There were a couple options: 2x6 wall with 6" of polyisocyanurate rigid foam to the outside There are some more difficult window installation details when your window is cantilevered over nothing but foam. Some long screws are need to attached a furring strip over the rigid foam (9" long) and those can add considerable cost to the project - upwards of $0.75 each The labels on rigid foam insulation scared me a little bit too -  15 YEAR LIMITED THERMAL WARRANTY Polyisocyanurate has the WORST embodied energy of the good types of insulation meaning it takes the most amount of energy to make relative to how much it will save This graph was posted on Green Bu...