Blower Door / Window Door Tests

Passive House Airtightness Achieved!

We ran a few different tests today to validate our airtightness numbers:

Our Field Measured Volume is 29356 CUFT

We did a Window Blower Door Test with the Duct Blaster

Here are photo's from our "Depressurization Test"

52 CFM50 - 0.106 ACH50


Here are photo's from our "Pressurization Test"

65 CFM50 - 0.133 ACH50

We also ordered the "D Ring" for the blower door to get an accurate Blower Door Number 
I should note - the tolerance for the D-Ring is:
125 CFM - 30 CFM

Here are photo's from our "Depressurization Test"
 
49 CFM50 - 0.100 ACH50


Here are photo's from our "Pressurization Test"



52 CFM50 - 0.106 ACH50

To average the results we are at 50.5 CFM50 

A few notes from the tests:

  • The blower door pressurization test was done in the protected breezeway door vs the duct blaster pressurization test that was done on the open back yard. 
  • We did a blower door pressure test up to 90 Pascals to see when/if the Studor Vents (AAV's) opening would effect our results - there was no noticeable difference:
  • The Blower Door Frame was extended fully to accommodate the width of our door. The seal was probably not perfect
  • All of our plumbing is not installed yet - we will do another test once it is.
  • We were having trouble syncing our computer to the manometer to complete a multi-point test, once we do that we will post those results!
From what I could find the tightest house in the world is in Alaska - 0.05 ACH50 - we are 25 CFM50 away from that.

Stay Tuned!



Comments

Popular posts from this blog

Window Installation

With all of the engineering and design that goes into a house like this, why would window installation be any different? EVERYTHING in a passive house is modeled, examined, and optimized thermodynamically. For now we will be talking about the thermodynamic analysis of the Passive House Windows and how this translates to the positioning of the windows within the wall system. A typical new construction window comes with a nailing flange that is part of the frame of the window. This requires the window to be nailed directly to the wall, resulting in the window being flush with the outer edge of the exterior wall. Passive House windows don't come with the nailing flange, this allows flexibility in location of installation within the wall system. The fact is, in a thick wall (12 inches or more, further details on wall thickness will be addressed in a later post) you typically don't want to install the window on the outside of your wall. You want to install the window in the middle o...

Wall Assembly 1

Double Wall Construction Maybe I am biased to double wall construction because the company I work for Airtight Services  is a cellulose insulation company; but it is still probably the most cost effective way to achieve the R-values necessary for Passive House. Based on our energy model we needed to achieve about an R-54 wall. There were a couple options: 2x6 wall with 6" of polyisocyanurate rigid foam to the outside There are some more difficult window installation details when your window is cantilevered over nothing but foam. Some long screws are need to attached a furring strip over the rigid foam (9" long) and those can add considerable cost to the project - upwards of $0.75 each The labels on rigid foam insulation scared me a little bit too -  15 YEAR LIMITED THERMAL WARRANTY Polyisocyanurate has the WORST embodied energy of the good types of insulation meaning it takes the most amount of energy to make relative to how much it will save This graph was posted on Green Bu...